Dwyer 616KD-00-V Differential Pressure Transmitter
Dwyer Instruments 616KD-00-V
Differential Press. Transmitter 0-1 in H2O, 0-10/0-5 V output
Order #: 616KD-00-V
Mfg #: 616KD-00-V
The Series 616KD Differential Pressure Transmitters with One-Touch technology are Designed for Simplicity making them the ideal choice for installers and maintenance professionals. The One-Touch Differential Pressure Transmitters are cost-effective, compact transmitters that reduce up front costs as well as expenses over the life of the product. These instruments not only alleviate cumbersome turn pots typically found in most transmitters, but eliminate entirely the need to span the instrument during calibration. With a single digital push button, both ZERO AND SPAN are calibrated properly, nothing else is required. No additional reference pressure sources and separate calibration devices are necessary; no need to remove from service and send to a lab. All that is required of the installer or user is to let the unit sit at zero reference pressure, then push a button. That is it! The transmitter is now ready for operation. Time savings are enormous over the life of the product compared to traditional transmitters which require time to annually remove the product from service plus the additional time to actually perform a complete full-span calibration. Mounting is simple with integral mounting holes on the 616KD that are inherent to the molded housing. The 616KD has the expanded capability to be mounted on a 35 mm DIN rail either via its side or back integral DIN rail clips. The Series 616KD has easy-to-wire open screw terminals at the top of the housing. An optional protective cap snaps directly to housing to cover terminals. The One-Touch family of Differential Pressure Transmitters are ideal for building automation applications such as air handlers, duct pressure, variable air volume and filter monitoring. Available models include ranges from 1 to 20 in H2O depending on series
Applications
Air handlers
Duct pressure
Variable air volume
Filter monitoring
Approvals
CE Approval
RoHS Letter of Compliance
Service: Air and non-combustible, compatible gases
Accuracy :2% FS
Stability :1% FS/year
Temperature Limits:0 to 140F (-17.8 to 60C)
Pressure Limits:2 psig
Thermal Effect0.06% FS/F, includes zero and span
Power Requirements:16 to 35 VDC (2 or 3 wire), 20 to 28 VAC (3 wire)
Output Signal:4 to 20 mA or option with field selectable 0 to 10, 0 to 5, 2 to 10, 1 to 5 V.
Zero and Span Adjustments:Push button
Loop Resistance :4 to 20 mA output (DC): 0 to 1250 max. Rmax = 50(VpsDC -10) ; 4 to 20 mA output (AC): 0 to 1200 max. Rmax = 50(1.4 VpsAC -12) ; Voltage output: 5K minimum
Current Consumption :21 mA max
Electrical Connections:Screw-type terminal block
Process Connections:Barbed, dual size to fit 1/8" & 3/16" (3 mm & 5 mm) ID rubber or vinyl tubing
Enclosure Ratin: NEMA1 (IP20)
Mounting Orientation :Vertical with pressure connections pointing down
Weight :1.8 oz (51 g)
Agency ApprovalCE