Dwyer 616KD-03 Differential Pressure Transmitter (616KD-03)
Dwyer 616KD-03 Differential Pressure Transmitter
The Series 616KD Differential Pressure Transmitters with One-Touchî Digital Push- Button Calibration Technology are designed for simplicity, making them the ideal choice for installers and maintenance professionals. These instruments not only alleviate cumbersome turn pots typically found in most transmitters, but eliminate entirely the need to span the instruments during calibration. With a single digital push button, both ZERO AND SPAN are calibrated properly, nothing else is required. No additional reference pressure sources or separate calibration devices are necessary.
Product Applications
Air handlers
Duct pressure
Variable air volume
Filter monitoring
Service:Air and non-combustible, compatible gases.
Wetted Materials:Consult factory.
Accuracy:616KD-A: ñ0.25% FS; 616KD-B: ñ1% FS, 616KD: ñ2%Â
FS.Stability:ñ1% FS/year.
Temperature Limits:0 to 140ðF (-17.8 to 60ðC).
Compensated Temperature Range:20 to 122ðF (-6.67 to 50ðC).
Pressure Limits:2 psig (ranges 5" w.c. or lower); 5 psig (ranges 10 to 40" w.c.).
Thermal Effect:616KD-A: ñ0.02% FS/ðF; 616KD-B: ñ0.04% FS/ðF; 616KD: ñ0.06% FS/ðF, includes zero and span.
Power Requirements:4-20 mA,output: 10 - 35 VDC (2 wire) or 12-26 VAC (4 wire); 5V,output: 10 - 35 VDC (3 wire) or 12-26 VAC (4 wire); 10VÂ
output: 13 - 35 VDC (3 wire) or 12-26 VAC (4 wire) for 616KD A and B. 16 to 36 VDC (2 or 3 wire): 20 to 28 VAC (3 wire) for 616KD.
Output Signal:4 to 20 mA or option with field selectable 0 to 10, 0 to 5, 2 to 10, 1 to 5 V.
Zero and Span Adjustments:Push button.
Loop Resistance:4 to 20 mA output (DC): 0 to 1250 é max. Rmax = 50(VpsDC -10) é; 4 to 20 mA output (AC): 0 to 1200 é max. Rmax = 50(1.4 VpsAC -12) é; Voltage output: 5K é minimum.
Current Consumption:24 mA max for 616KD A and B. 21 mA max for 616KD.
Electrical Connections:Screw-type terminal block.
Process Connections:Barbed, dual size to fit 1/8" & 3/16" (3 mm and 5 mm) ID rubber or vinyl tubing.
Enclosure Rating:NEMA 1 (IP20).
Mounting Orientation:Vertical with pressure connections pointing down.
Weight:1.8 oz (51 g).
Agency Approval:CE, optional plenum rated units meet UL Standard 2043.